Printable PDF
ORC Series Outdoor Air-Cooled Remote Condensers
Standard Features
- TEFC PERMANENTLY LUBRICATED MOTOR
- COMPUTER DESIGNED CONDENSER COILS
- BELT DRIVE BLOWER WITH SEALED-FOR-LIFE BEARINGS
- FULL FLOODING SYSTEM MINUS 20" FAHRENHEIT
WHY A REMOTE CONDENSER
The DCA Dehumidification system performs functions other than dehumidification. When dehumidifiers operate they discharge warm dry air to the conditioned space. During cold months this heating can go a long way in helping to produce a warm and comfortable room environment. When this heating is not desirable or cannot be directed to an area where it is needed, the DCA Remote Condenser provides the solution.
THE REMOTE CONDENSER SOLUTION
During the warm months or when the dehumidified space becomes over-heated, a DCA Remote Condenser is needed. The Remote Condenser allows the dehumidifier to discharge cool dry air to the conditioned space. An automatic change-over room thermostat (optional) controls the room temperature. Normally the Remote Condenser is located outdoors and is connected to the dehumidifier by two copper freon lines. Because of advanced technology, the Remote Condenser can be operated under conditions as extreme as -20°F.
ORC SERIES CONDENDER SELECTION GUIDE
DCA Model
Number |
H.P. |
Line Sets (O.D.) |
95°F Ambient Model |
100°F Ambient Model |
105°F Ambient Model |
MBH |
| Supply |
Return |
| DCA500/500WH |
1.5 |
5/8" |
3/8" |
ORC-050 |
ORC-090 |
ORC-090 |
22.41 |
| DCA900/900WH |
2 |
5/8" |
3/8" |
ORC-090 |
ORC-140 |
ORC-200 |
32.51 |
| DCA1400/1400WH |
3 |
5/8" |
1/2" |
ORC-140 |
ORC-200 |
ORC-200 |
44.56 |
| DCA2000/2000WH |
4 |
5/8" |
1/2" |
ORC-200 |
ORC-250 |
ORC-300 |
62.25 |
| DCA2500/2500WH |
5 |
7/8" |
1/2" |
ORC-250 |
ORC-300 |
LORC-10 |
77.61 |
| DCA3000/3000WH |
6 |
7/8" |
5/8" |
ORC-300 |
ORC-330 |
LORC-12 |
86.23 |
| DCA3300/3300WH |
7.5 |
7/8" |
5/8" |
ORC-330 |
LORC-10 |
LORC-12 |
110.18 |
| DCA3500/3500WH |
7.5 |
7/8" |
5/8" |
ORC-330 |
LORC-10 |
LORC-12 |
110.18 |
DIAGRAMS

DIMENSIONS IN INCHES
CONDENSER
MODEL # |
A |
B |
C |
D |
E |
F |
G |
H |
I |
J |
SHIPPING
WEIGHT (LBS) |
| ORC-050 |
25 |
28 |
22 |
20 |
22 |
10.25 |
9.25 |
5.5 |
4.65 |
2 |
155 |
| ORC-090 |
30 |
45 |
25 |
20.5 |
28 |
13.5 |
15.625 |
5.5 |
10 |
2 |
235 |
| ORC-140 |
30 |
45 |
25 |
20.5 |
28 |
13.5 |
15.625 |
5.5 |
10 |
2 |
260 |
| ORC-200 |
30 |
45 |
25 |
22.5 |
40 |
13.5 |
15.625 |
5.5 |
10 |
2 |
260 |
| ORC-250 |
30 |
45 |
25 |
22.5 |
40 |
13.5 |
15.625 |
5.5 |
10 |
2 |
320 |
| ORC-300 |
38 |
46 |
32 |
30.5 |
40 |
16 |
18.5 |
8 |
7 |
2 |
350 |
| ORC-330 |
38 |
46 |
32 |
30.5 |
40 |
16 |
18.5 |
8 |
7 |
2 |
350 |
BLOWER AND MOTOR DATA
| |
ORC-050 |
ORC-090 |
ORC-140 |
ORC-200 |
ORC-250 |
ORC-300 |
ORC-330 |
| BLOWER HORSEPOWER |
1/2 |
1/2 |
1/2 |
1 |
1.5 |
1.5 |
1.5 |
| |
208/320 - 1 PH |
4.4 |
4.4 |
4.4 |
6.4 |
8.6 |
8.6 |
8.6 |
| FLA |
208/230 - 3 PH |
N/A |
2 |
2 |
3.4 |
4.6 |
4.6 |
4.6 |
| 60 HZ |
460 3 PH |
N/A |
1 |
1 |
1.7 |
2.3 |
2.3 |
2.3 |
| |
575 3 PH |
N/A |
N/A |
N/A |
1.4 |
1.9 |
1.9 |
1.9 |
| |
208/230 - 1 PH |
5.5 |
5.5 |
5.5 |
8 |
10.75 |
10.75 |
10.75 |
| MINIMUM |
208/230 - 3 PH |
N/A |
2.5 |
2.5 |
4.2 |
5.75 |
5.75 |
5.75 |
| AMPACITY |
460 3 PH |
N/A |
1.25 |
1.25 |
2.1 |
2.9 |
2.9 |
2.9 |
| |
575 3 PH |
N/A |
N/A |
N/A |
1.75 |
2.2 |
2.2 |
2.2 |
| |
208/230 - 1 PH |
10 |
10 |
10 |
14 |
15 |
15 |
15 |
| MAX FUSE |
208/230 - 3 PH |
N/A |
5 |
5 |
8 |
8 |
8 |
8 |
| SIZE |
460 3 PH |
N/A |
3 |
3 |
4 |
4 |
4 |
4 |
| |
575 3 PH |
N/A |
N/A |
N/A |
4 |
4 |
4 |
4 |
| C.F.M. |
1200 |
1600 |
2300 |
3200 |
4000 |
5000 |
5000 |
| BLOWER SIZE |
10" |
12" |
12" |
12" |
12" |
15" |
15" |
| BLOWER R.P.M. |
590 |
428 |
582 |
591 |
731 |
563 |
554 |
| MBH @ 25 DIFF. |
22.412 |
32.506 |
41.263 |
62.248 |
77.609 |
89.825 |
98.378 |
| MBH @ 30 DIFF. |
26.894 |
39.007 |
49.515 |
74.697 |
86.232 |
107.79 |
118.053 |
|